Table 3-8. Power Consumption of the Analog Input Module

I/O Module

Power Consumption (mW)

Quantity

Used

Duty

Cycle

Sub-Total

(mW)

Description

P

TYPICAL

Analog Input

AI Module Base

84 mA @ 12 volts dc

1008 mW

Jumper set for +T @ 12 volts dc

Channel 1

Channel’s mA current

draw from +T * 1.25 * 12

Channel 2

Channel’s mA current

draw from +T * 1.25 * 12

Channel 3

Channel’s mA current

draw from +T * 1.25 * 12

Channel 4

Channel’s mA current

draw from +T * 1.25 * 12

Jumper set for +T @ 24 volts dc

Channel 1

Channel’s mA current

draw from +T * 2.50 * 12

Channel 2

Channel’s mA current

draw from +T * 2.50 * 12

Channel 3

Channel’s mA current

draw from +T * 2.50 * 12

Channel 4

Channel’s mA current

draw from +T * 2.50 * 12

Table Total

Duty Cycle

The duty cycle is based on the average current flow compared to the

full-scale current flow value. To approximate the duty cycle, estimate

the average current consumption in relation to its maximum range. For

example, if an AI channel’s current averages 16 mA:

Duty Cycle = Average mA output

÷

Maximum mA Output = (16

÷

20) = 0.80