Power Connections

3-21

Table 3-13. Power Consumption of the High and Low Speed Pulse Input Module

I/O Module

Power Consumption (mW)

Quantity

Used

Duty

Cycle

Sub-Total

(mW)

Description

P

TYPICAL

PI Module

21 mA @ 12 volts dc No

Channels Active

252 mW

Channel 1

7.4 mA

88.8 mW

Channel 2

7.4 mA

88.8 mW

Per Active LED –

Maximum 4

1.5 mA

18 mW

Jumper set to +T @ 12

volts dc

1.25 * Measured Current

Draw at +T Terminal

Jumper set to +T @ 24

volts dc

2.5 * Measured Current

Draw at +T Terminal

Table Total

Duty Cycle

The duty cycle is the time on divided by the total time, and is

essentially the percent of time that the I/O channel is active

(maximum power consumption).

Duty Cycle = [Active Time * (Signals Duty Cycle)]

÷

(Total Time Period)

For example, if a Pulse Input receives a signal for 6 hours over a 24-

hour time period and the signal’s wave form is on time for 1/3 of the

signal’s period:

Duty Cycle = [6 hours * (1

÷

3)]

÷

(24 hours) = 0.0825