ROC800-Series Instruction Manual
Revised Jul-14
Power Connections
3-21
Table 3-13. Power Consumption of the High and Low Speed Pulse Input Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
PI Module
21 mA @ 12 volts dc No
Channels Active
252 mW
Channel 1
7.4 mA
88.8 mW
Channel 2
7.4 mA
88.8 mW
Per Active LED –
Maximum 4
1.5 mA
18 mW
Jumper set to +T @ 12
volts dc
1.25 * Measured Current
Draw at +T Terminal
Jumper set to +T @ 24
volts dc
2.5 * Measured Current
Draw at +T Terminal
Table Total
Duty Cycle
The duty cycle is the time on divided by the total time, and is
essentially the percent of time that the I/O channel is active
(maximum power consumption).
Duty Cycle = [Active Time * (Signals Duty Cycle)]
÷
(Total Time Period)
For example, if a Pulse Input receives a signal for 6 hours over a 24-
hour time period and the signal’s wave form is on time for 1/3 of the
signal’s period:
Duty Cycle = [6 hours * (1
÷
3)]
÷
(24 hours) = 0.0825