Background Image
Table of Contents Table of Contents
Previous Page  72 / 182 Next Page
Information
Show Menu
Previous Page 72 / 182 Next Page
Page Background

ROC800-Series Instruction Manual

3-20

Power Connections

Revised Jul-14

Table 3-12. Power Consumption of the Discrete Output Relay Module

I/O Module

Power Consumption (mW)

Quantity

Used

Duty

Cycle

Sub-Total

(mW)

Description

P

TYPICAL

DOR Module

6.8 mA @ 12 volts dc

No Channels Active

81.6 mW

Channel 1

150 mA for 10 mSec

during transition

1800 mW

for 10 mSec

Channel 2

150 mA for 10 mSec

during transition

1800 mW

for 10 mSec

Channel 3

150 mA for 10 mSec

during transition

1800 mW

for 10 mSec

Channel 4

150 mA for 10 mSec

during transition

1800 mW

for 10 mSec

Channel 5

150 mA for 10 mSec

during transition

1800 mW

for 10 mSec

Per Active LED –

Maximum 5

1.5 mA

18 mW for

10 mSec

Table Total

Duty Cycle

The duty cycle is:

[((Number of Transitions in some time period) * 0.01 sec)]

÷

(Seconds in the period) = Duty Cycle

For example, if a DOR channel changes state 80 times per hour:

80 = Number of transitions.

Hour is the time period.

An hour contains 3600 seconds.

Calculate the duty cycle as:

Duty Cycle = [(80 * 0.01)

÷

3600] = 0.0002