ROC800-Series Instruction Manual

3-22

Power Connections

Revised Jul-14

Table 3-14. Power Consumption of the MVS Module

I/O Module

Power Consumption (mW)

Quantity

Used

Duty

Cycle

Sub-Total

(mW)

Description

P

TYPICAL

MVS Module

112 mA @ 12 volts dc

1344 mW

Per Active LED – Maximum 2

1.5 mA

18 mW

Power provided by the module

for the MVS sensors

1.25 * Measured

Current Draw at +

Terminal

1

Table Total

Note

:

For an MVS sensor, the typical mW per MVS is about 300 mW.

Duty Cycle

The duty cycle is the time on divided by the total time. For an MVS,

the sensor is always drawing power, so enter the duty cycle as “1” for

the MVS power calculations. The LEDs can also have an associated

duty cycle, which is essentially the percent of time that the LEDs are

active.

Duty Cycle = Active time

÷

(Active time + Inactive time)

For example, if the LEDs are on approximately 20 minutes a day:

Duty Cycle = 20 minutes

÷

(24 * 60 minutes in a day) = 20

÷

1440 = 0.014

Table 3-15. Power Consumption of the MVS I/O Module

I/O Module

Power Consumption (mW)

Quantity

Used

Duty

Cycle

Sub-Total

(mW)

Description

P

TYPICAL

MVS Module

27 mA @ 12 volts dc

325 mW

0 ,1, 2

1

Power provided by the module

for the MVS sensors

300 mW

1 – 12

1

Table Total

Note

:

For an MVS sensor, the typical mW per MVS is about 300 mW.