ROC800-Series Instruction Manual

3-12

Power Connections

Revised Jul-14

individual worksheets to determine how to best “tune” your

configuration and lessen power demands.

General Calculation

Process

To calculate the power requirements of a ROC800 configuration

requires:

1.

Determine the kind and number of communication modules and the

kind and number of expanded backplanes you are implementing.

Enter those values in the Quantity Used column of

Table 3-5

.

2.

Multiply the P

Typical

value by the Quantity Used. Enter the values in

the Sub-Total column of

Table 3-5

. Perform this calculation for

both

the communications module and the LED.

3.

Determine the kind and number of I/O modules you are

implementing and complete

Tables 3-6

through

3-20

for those

modules. For each applicable I/O module:

a.

Calculate the P

Typical

values and enter them in the P

Typical

columns of each table. Perform this calculation for the I/O

modules, LEDs (if applicable), channels (if applicable), and any

other devices.

b.

Calculate the Duty Cycle value for each I/O module and each

I/O channel (as applicable). Enter those values in the Duty Cycle

column of

Tables 3-6

through

3-20

.

c.

Multiply the P

Typical

values by the Quantity Used by the Duty

Cycle on each applicable table. Enter those individual sub-totals

in the Sub-Total column on each table and add the sub-totals to

calculate the Total for the table.

4.

Transfer the totals from

Tables 3-6

through

3-20

to their respective

lines in the Sub-Total column on

Table 3-5

.

5.

Add the Sub-Total values for

Tables 3-6

through

3-20

. Enter that

value in the Total for All Modules line on

Table 3-5

.

6.

Add the value from the Total for ROC800 Base Unit to the Total for

All Modules. Enter that result in the Total for ROC800 Base Unit

and All Modules line.

7.

Transfer the Other Devices total from

Table 3-20

to its respective

line in the Sub-Total column on

Table 3-5

.

8.

Add the values from Total for ROC800 Base Unit, Total for All

Modules, and the total for Other Devices. Enter that value in the

Total for ROC800 Base Unit, All Modules, and Other Devices line.

9.

Multiply the value in the Total for ROC800 Base Unit, Total for All

Modules, and Other Devices by 0.25. Enter the result in the Power

System Safety Factor (0.25) line.

Note

:

This value represents a safety factor to the power system to

account for losses and other variables not factored into the

power consumption calculations. This safety factor may vary