ROC800-Series Instruction Manual

Revised Jul-14

Input/Output Modules

4-11

The DI module provides a source voltage for dry relay contacts or for an

open-collector solid-state switch.

The DI module’s LEDs light when each input is active.

Each DI channel can be software-configured to function as a momentary

or latched DI (see the

ROCLINK 800 Configuration Software User

Manual (for ROC800-Series)

, Part Number D301250X012 or the

ROCLINK 800 Configuration Software User Manual (for ROC800L),

Part Number D301246X012). A latched DI remains in the active state

until reset. Other parameters can invert the field signal and gather

statistical information on the number of transitions and the time

accumulated in the on- or off-state.

Caution

The Discrete Input module is designed for use with “dry” relay contacts

or solid-state switches. Applied voltage in excess of 24 Vdc may

damage the module.

The DI module senses the current flow, which signals the ROC800

electronics that the relay contacts have closed. The opening of the

contacts interrupts the current flow and the DI module signals the

ROC800 electronics that the relay contacts have opened. Using

ROCLINK 800, you can set the scan rate between 4 and 43200

milliseconds.

The left side of

Figure 4-9

displays the internal circuitry while the right

side displays possible field wiring.

Figure 4-9. Discrete Input Module Field Wiring

Caution

You can induce ground loops by tying commons from various modules

together.

+

-

DRY CONTACT

ROC800 POWERED

+

-

+V

6.6KW

DOC0507A

COM

6

8

7

4

5

3

2

1

DI

8 CHAN

OPEN DRAIN TYPE DEVICE

OR

OPEN COLLECTOR

EXTERNALLY POWERED