ROC800-Series Instruction Manual

4-6

Input/Output Modules

Revised Jul-14

If the slot is currently empty, remove the module cover.

3.

Insert the new I/O module through the module slot on the front of

the ROC800 or EXP housing. Make sure the label on the front of the

module faces right side up (refer to

Figure 4-3

). Gently slide the

module in place until it contacts properly with the connectors on the

backplane.

Note

:

If the module stops and will not go any further,

do not

force

the module. Remove the module and see if the pins are bent.

If the pins are bent, gently straighten the pins and re-insert

the module. The back of the module

must

connect fully with

the connectors on the backplane.

Figure 4-3. Installing an I/O Module

4.

Tighten the captive screws on the front of the module.

5.

Wire the I/O module (refer to

Wiring I/O Modules

).

6.

Replace the wire channel cover.

Caution

Never connect the sheath surrounding shielded wiring to a signal

ground terminal or to the common terminal of an I/O module. Doing so

makes the I/O module susceptible to static discharge, which can

permanently damage the module. Connect the shielded wiring sheath

only to a suitable earth ground.

7.

Connect to ROCLINK 800 software and login. The I/O modules are

self-identifying after re-connecting to ROCLINK 800 software.

8.

Configure the I/O point.