ROC800-Series Instruction Manual

4-8

Input/Output Modules

Revised Jul-14

D301250X012) or the

ROCLINK 800 Configuration Software User

Manual (for ROC800L)

(Part Number D301246X012).

Note

:

The AI-16 module provides 16-bit resolution and uses a 24-bit

A/D converter. DIP switches on the AI-16 module (see

Figure 4-

6

) allow you to select between current and voltage loop input.

You can configure the AI (+T) module as either 12 or 24 Volt dc using

jumper J4 on the AI-12 module (see

Figure 4-4

). The AI modules can

provide isolated +12 Volt dc or +24 Volt dc field transmitter power on a

per-module basis. For example, one module can provide +12 Volts dc

for powering low power analog transmitters, while another module in

the same ROC800 can provide +24 Volts dc for powering conventional

4–20-mA transmitters. Refer to

Figure 4-5

.

A

12 / 24 V dc Jumper

Figure 4-4. AI-12 Jumper J4 (Shown Set to +12V)

Figure 4-5. Analog Input Module Field Wiring (AI-12 and AI-16)

1-5 VOLT DEVICE

EXTERNALLY POWERED

+

-

1-5 VOLT DEVICE

ROC800 POWERED

+

-

ROC800 POWERED

CURRENT LOOP DEVICE 4-20mA

-

+

OUT SIGNAL

COM

IN

DOC0506C

+

+

+

OUT SIGNAL

COM

1-5 VOLT DEVICE

EXTERNALLY POWERED

1-5 VOLT DEVICE

ROC800 POWERED

CURRENT LOOP DEVICE 4-20mA

ROC800 POWERED

-

-

-

IN

DOC0514B

250

250

250

250

Precision

Resistor

A