Background Image
Table of Contents Table of Contents
Previous Page  94 / 182 Next Page
Information
Show Menu
Previous Page 94 / 182 Next Page
Page Background

ROC800-Series Instruction Manual

Revised Jul-14

Input/Output Modules

4-9

On the AI-16 module, you use jumper J3 to configure the AI (+T) as 12

or 24 Volts dc. Additionally, two DIP switches on the module allow you

to select between current and voltage loop input.

A

I indicates current loop input; V indicates voltage

loop input

Figure 4-6. AI-16 DIP Switches

Caution

You can induce ground loops by tying commons from various modules

together.

4.4 Analog Output (AO) Modules

The 16-bit Analog Output (AO) module has four channels that provide a

current output for powering analog devices. Analog outputs are analog

signals the ROC800 generates to regulate equipment, such as control

valves or any device requiring analog control.

Each channel on this module provides a 4 to 20 mA current signal for

controlling analog current loop devices. The AO module isolation

includes the power supply connections.

Note

:

AO modules (Part Number W38199) labeled

AO-16

are an

earlier version that controls the low side current. AO modules

(Part Number W38269) labeled

AO

are a newer version

(January 2005 and later) that provides and controls the high side

current.

The AO module includes a moveable jumper (see

Figure 4-7

). Set the

jumper to 12V if the transmitter load is 300Ω or less. Set the jumper to

24V if the transmitter load exceeds 300Ω.

A