Background Image
Table of Contents Table of Contents
Previous Page  98 / 182 Next Page
Information
Show Menu
Previous Page 98 / 182 Next Page
Page Background

ROC800-Series Instruction Manual

Revised Jul-14

Input/Output Modules

4-13

Figure 4-11. Externally Powered Pulse Input Module Field Wiring

Figure 4-12. ROC800-Powered Pulse Input Module Field Wiring

Caution

You can induce ground loops by tying commons from various modules

together.

4.7 Discrete Output (DO) Modules

The five-channel Discrete Output (DO) module provides two-state

outputs to energize solid-state relays and power small electrical loads.

These are solid-state relays. A Discrete Output may be set to send a

pulse to a specified device. Discrete Outputs are high and low outputs

used to turn equipment on and off.

DO modules can be software-configured as latched, toggled,

momentary, or Timed Duration Outputs (TDO). The DO can be

+

-

OPEN DRAIN TYPE

OR

OPEN COLLECTOR DEVICE

EXTERNALLY POWERED

+

-

CONTACT-CLOSURE DEVICE

EXTERNALLY POWERED

125KHz PI FILTER &

LEVEL DETECTION

12KHz PI FILTER &

LEVEL DETECTION

DOC0510B

+

-

12KHz PI FILTER &

LEVEL DETECTION

+T

METER COIL

- +

DOC0511A

H

L

H

L

COM

CH 2

CH 1

+T

PI

2 CHAN

OPEN DRAIN TYPE DEVICE

OR

OPEN COLLECTOR

ROC800 POWERED

COM

Representative

Internal Circuit

Field Wiring

Representative

Internal Circuit

Field Wiring