Natural Gas Technologies - Solutions for the Natural Gas Industry - page 28

28
Type CSB400
Spring-Loaded Pressure Reducing Regulators
Introduction
The CSB400 Series direct-operated,
spring-loaded regulators have been
engineered to fit a multitude of
pressure-reducing applications including
commercial and industrial installations.
This flexibility is provided by the
numerous body sizes and end
connections, outlet pressure settings, as
well as the option for internal, external,
or dual pressure registration.
In addition to application flexibility, the
CSB400 Series offersmultiple overpressure
protection options tomeet your demands
on application requirements.
The CSB400 Series is in conformity with
the Pressure Equipment Directive PED
97/23/EC. The base regulator is classified
under Category I, the regulator with
slam-shut module is classified under
Category IV.
Body Sizes andEndConnection Styles
Ductile Cast Iron:
1, 1-1/4, 1-1/2, or 2 NPT, Rp 1, 1 x 1-1/4,
1-1/4, 1-1/2, or 2, Rp 1 x 2-1/4 GAZ, NPS
1-1/2 (DN 40), PN16, NPS 2 (DN 50),
CL125 FF, CL150 FF, or PN 10/16
Steel:
1, 1-1/4 or 1-1/2 NPT, Rp 1, 1-1/4 or 1-1/2
MaximumOperating Inlet Pressure
Differential Strength
6 bar to 16 bar (depending on type)
Maximum Emergency Inlet
Pressure Differential Strength
10 bar to 20 bar (depending on type)
Outlet Pressure Range
17 mbar to 3 bar
Maximum Emergency Outlet
Pressure (Casing)
4 bar
MaximumOutlet Pressure to avoid
Internal Parts Damage
0.34 bar over set‑point
• Slam-shut
• Ductile Cast Iron andWCC
Steel Bodies Available
• Wide Variety of Body
Sizes and End Connections
• No Special Tools for
Pressure Adjustment and
Orifice Removal
Features
MaximumOperatingOutlet Pressure
3 bar
Pressure Registration
Internal, external or dual
Temperature Capabilities
According to PED Standards:
-20° to 60°C
Non-PED:
-30° to 66°C
Approximate Weights
Threaded Body:
Type CSB400:
4 kg
Type CSB403:
9 kg
Type CSB404:
5 kg
Flanged Body:
Add 4 kg to weights listed above
Type VSX4 Slam-Shut Module
Specifications
Standard Overpressure Shutoff (OPSO)
Set Value:
43 to 3400 mbar
Standard Underpressure Shutoff
(UPSO) Set Value:
10 to 1500 mbar
Connections
Slam-Shut Vent:
1/4 NPT
External Sensing Line:
1/4 NPT
Casing Material
Aluminum
Pressure Registration
Internal or external
For full details consult the documenta-
tion available on our website:
Type CSB400
Type CSB404