Natural Gas Technologies - Solutions for the Natural Gas Industry - page 27

27
TM
Introduction
The RP Series regulators are direct‑oper-
ated with non-balanced trim. Normally
they are fitted with a built-in filter.
They are produced in the following ver-
sion: types RP/011, RP/022, and RP/033.
All models can be fitted with a shutoff
valve.
The RP Series is in conformity with the
Pressure Equipment Directive PED 97/23/
EC and is classified under Category I
maximum.
Available Configurations
Types RP/011, RP/022, and RP/033:
Regulator
Types RP/011/66, RP/022/66, and
RP/033/66:
Regulator + Shutoff
Body Sizes andEndConnection Styles
Type RP/011:
1 x 1-1/4" BSP Threaded
Type RP/022:
1-1/4 x 2" BSP Threaded
Type RP/033:
2 x 3" BSP Threaded
Type RP/011-FS:
DN 25 x 32 PN 16, 25, 40 / CL150, CL300
Flanged
Type RP/022-FS:
DN 32 x 50 PN 16, 25, 40 / CL150, CL300
Flanged
Type RP/033-FS:
DN 50 x 80 PN 16, 25, 40 / CL150, CL300
Flanged
Inlet Pressure
Body Allowable Pressure: Up to 20 bar
Actuator Allowable Pressure: 4 bar
Maximum Inlet Pressure: 20 bar
Inlet Pressure Range: 0.2 to 20 bar
• Overpressure and
Underpressure Shutoff
Valve
• Manual Reset
• Inlet and Outlet In-line
Features
Outlet Pressure Ranges
Types RP/022 and RP/033:
0.1 to 4 bar
Type RP/011:
0.1 to 2 bar
Accuracy Class
Up to ±5%
Lock-Up Pressure Class
Up to 10%
Built-in Shutoff Valve
Independent Pneumatic Control
Accuracy Group: ±5%
Response Time: <1 s
Temperature Capabilities
Standard Version:
Working: -10° to 60°C
Low Temperature Version:
Working: -20° to 60°C
Approximate Weights
6 to 25 kg
For full details consult the documenta-
tion available on our website:
Type RP/022
Type RP/033/66-fs
RP Series
Spring-Loaded Pressure Reducing Regulators
1...,17,18,19,20,21,22,23,24,25,26 28,29,30,31,32,33,34,35,36,37,...56