ROC800-Series Instruction Manual

4-26

Input/Output Modules

Revised Jul-14

Figure 4-32. AC I/O Module (Output Field Wiring)

Note

:

If the label on your AC I/O module

does not

indicate 120/240V,

your module is designed for use

only

with 120V. Additionally,

all AC wiring must be shielded.

AC Discrete Inputs

You can configure each channel as an AC input/detector. Each

channel can detect the presence of an AC signal between 90 and 265

Vrms at 47 to 63 Hz. In discrete input mode the module monitors the

status of various AC sources.

You can also software-configure each channel to function as a latched

DI, which remains in active state until reset. Other parameters can invert

the field signal and gather statistical information on the number of

transitions and the time accumulated in the on or off state. The fastest

time that each channel within the module can be read is 20 times per

second. See

Figure 4-33.