ROC800-Series Instruction Manual

4-24

Input/Output Modules

Revised Jul-14

Figure 4-30. MVS Jumper J4 (Shown Not Terminated)

Four wires run from the MVS module terminal block and connect to the

sensor. The wires should be a minimum size of 22 AWG and a

maximum length of 1220 m (4000 ft).

Note

:

Insulated, shielded, twisted-pair wiring is required when using

MVS signal lines.

Two of the terminal blocks provide power and the other two terminals

provide a communication path.

Table 4-5

identifies the terminals.

Table 4-4. MVS Signal Routing

Label

MVS

LED

Terminal

A

RX / TX +

Lit green when receiving

1

B

RX / TX –

N/A

2

None

No Connect

Lit green when transmitting

3

+

Sensor Power

N/A

4

Common

N/A

5

Note

:

Pay close attention to the connections; do not reverse the

power wires.

Make

these connections only

after removing

power

from the ROC800. Double-check connections for the

proper orientation before applying power. If the connections are

reversed and power is applied, you may damage

both

the MVS

module and the ROC800-Series processor board.

Caution

You can induce ground loops by tying commons from various modules

together.