ROC800-Series Instruction Manual

Revised Jul-14

Inputs and Outputs

6-9

14.

Select the

General

tab on the Analog Output screen.

15.

Remove the test equipment, and reconnect the field device.

16.

If possible, verify the correct operation of the AO module by setting

the values in the High Reading EU and Low Reading EU fields to the

values you recorded in step 9 and observing the field device.

6.3.5 Troubleshooting Discrete Input Modules

Equipment Required

:

Jumper wire

PC running ROCLINK 800 software

Caution

Failure to exercise proper electrostatic discharge precautions, such as

wearing a grounded wrist strap may reset the processor or damage

electronic components, resulting in interrupted operations.

1.

Disconnect the field wiring at the DI module terminations.

2.

Connect to ROCLINK 800 software.

3.

Select

Configure

>

I/O

>

DI Points

. The Discrete Input screen

displays.

Note

:

You can also click the graphic image of the module to display

this screen.

4.

Select the appropriate Discrete Input Point number.

5.

Place a jumper across a channel input terminal (1-8) and COM. The

value in the Status field should change to

On

.

6.

Remove the jumper between the channel terminal and COM. The

value in the Status field should change to

Off

.

7.

Remove the test equipment, and reconnect the field device.

6.3.6 Troubleshooting Discrete Output Modules

Equipment Required

:

Multimeter

PC running ROCLINK 800 software

Caution

Failure to exercise proper electrostatic discharge precautions, such as

wearing a grounded wrist strap may reset the processor or damage

electronic components, resulting in interrupted operations.

1.

Verify the load current requirement does not exceed the current limit

value of the module.

2.

Verify that you have correctly wired the module.