ROC800-Series Instruction Manual

6-10

Inputs and Outputs

Revised Jul-14

3.

Remove all wiring from the DO module.

4.

Connect the multimeter set up to measure ohms to the channel that

you are testing.

5.

Measure the resistance with the DO Status OFF. It should be over 2

megohms.

6.

Measure the resistance with the DO Status ON. It should be

approximately 1 ohm.

6.3.7 Troubleshooting Discrete Output Relay Modules

Equipment Required

:

Multimeter

PC running ROCLINK 800 software

Caution

Failure to exercise proper electrostatic discharge precautions, such as

wearing a grounded wrist strap may reset the processor or damage

electronic components, resulting in interrupted operations.

1.

Connect the multimeter set up to measure ohms to the channel that

you are testing.

2.

Set the Status to

On

and click

Apply

.

3.

Measure the resistance across the + and

terminals. You should have

a reading of 0 (zero) ohms with an indication of continuity.

4.

Measure the resistance across the + and – terminals. You should have

a reading of an open circuit with no continuity indicated.

6.3.8 Troubleshooting Pulse Input Modules

Equipment Required

:

Pulse Generator

Voltage Generator

Frequency Counter

Jumper wire

PC running ROCLINK 800 software

Caution

Failure to exercise proper electrostatic discharge precautions, such as

wearing a grounded wrist strap may reset the processor or damage

electronic components, resulting in interrupted operations.

To verify high-speed operation:

1.

Disconnect the field wiring at the PI module terminations.

2.

Connect to ROCLINK 800 software.