ROC800-Series Instruction Manual

Revised Jul-14

Communications

5-11

used to multi-drop units on a serial network over long distances using

inexpensive twisted-pair wiring.

EIA-422 (RS-422) drivers are designed for party-line applications

where one driver is connected to, and transmits on, a bus with up to ten

receivers. EIA-422 (RS-422) allows long distance point-to-point

communication and the drivers are designed for true multi-point

applications with up to 32 drivers and 32 receivers on a single bus.

The default values for EIA-422/485 (RS-422/485) communication are

19200 baud rate, 8 data bits, 1 stop bit, and no parity. The maximum

rate is 57.6 Kbps.

EIA-422/485 (RS-422/485) communication modules include LED

indicators that display the status of receive and transmit activity. Refer

to

Tables 5-8

and

5-9

.

Table 5-8. EIA-422 (RS-422) Signal Routing – Comm3, Comm4, and Comm5

Signal

RS-422

Function

Terminal

A

RX +

Lit when module (Comm3, Comm4, or Comm5) is currently receiving.

1

B

RX –

None.

2

Y

TX +

Lit when module (Comm3, Comm4, or Comm5) is currently transmitting.

3

Z

TX –

None.

4

COM

Common Ground.

5

Table 5-9. EIA-485 (RS-485) Signal Routing – Comm3, Comm4, and Comm5

Signal

RS-485

Function

Terminal

A

RX / TX + Lit when module (Comm3, Comm4, or Comm5) is currently receiving.

1

B

RX / TX – None.

2

Y

No Connect Lit when module (Comm3, Comm4, or Comm5) is currently transmitting.

3

Z

No Connect None.

4

COM

Common Ground.

5

Caution

You can induce ground loops by tying commons from various modules

together.

EIA-422/485 (RS-422/485) communication provides EIA-422/485 (RS-

422/485) signals on the Comm3, Comm4, or Comm5 port, depending

on where you have installed the module. Wiring should be twisted-pair

cable, one pair for transmitting, and one pair for receiving. The EIA-422

(RS-422) module uses four wires and the EIA-485 (RS-485) uses two

wires for connectivity.

5.8.1 EIA-422/485 (RS-422/485) Jumpers & Termination Resistors

Four jumpers—J3, J4, J5, and J6—are located on the EIA-422/485 (RS-

422/485) communication module (see

Figure 5-5

). These jumpers

determine the mode in which the module runs (RS-422 or RS-485) and

if the module is terminated.