ROC800-Series Instruction Manual

Revised Jul-14

Communications

5-9

designed so that you do not need to be concerned about cable crosstalk,

provided the cable meets all other requirements.

Noise can be caused by crosstalk of externally induced impulses.

Impulse noise may cause data errors if the impulses occur at very

specific times during data transmission. Generally, do not be concerned

about noise. If you suspect noise related data errors, it may be necessary

to either reroute the cable or eliminate the source of the impulse noise.

Multi-pair, PVC 24 AWG telephone cables have an attenuation of

approximately 8 to 10 dB/100 m at 200°C (392°F). The attenuation of

PVC insulted cable varies significantly with temperature. At

temperatures greater than 400°C (752°F), use plenum-rated cables to

ensure that cable attenuation remains within specification.

When connecting two twisted-pair Medium Attachment Units (MAUs)

or repeaters together over a segment, wire the transmit data pins of one

eight-pin connector to the receive data pins of the other connector, and

vice versa. There are two methods for accomplishing 10BASE-T

crossover wiring:

Using special cable.

Wiring the 10BASE-T crossover inside the hub.

For a single segment connecting only two devices, provide the signal

crossover by building a special crossover cable, wire the transmit data

pins of one eight-pin connector to the receive data pins of the other

connector, and vice versa. Refer to

Figure 5-4

.

Signal

Signal

Pin 1 TD+

Pin 1 TD+

Pin 2 TD–

Pin 2 TD–

Pin 3 RD+

Pin 3 RD+

Pin 6 RD–

Pin 6 RD–

Figure 5-4. 10BASE-T Crossover Cable

5.7 EIA-232 (RS-232) Serial Communication

The built-in EIA-232 (RS-232), the LOI, and the communication

modules meet all EIA-232 (RS-232) specifications for single-ended,

asynchronous data transmission over distances of up to 15 meters (50

feet). EIA-232 (RS-232) communication provides transmit, receive, and

modem control signals. The LOI port also meets EIA-232D (RS-232D)

specifications.

EIA-232 (RS-232) communication has the following communication

port designations in ROCLINK 800.

LOI

– Local Port EIA-232 (RS-232D). Refer to

Section 5.5, Local

Operator Interface

.