Background Image
Table of Contents Table of Contents
Previous Page  119 / 182 Next Page
Information
Show Menu
Previous Page 119 / 182 Next Page
Page Background

ROC800-Series Instruction Manual

4-34

Input/Output Modules

Revised Jul-14

The IEC 62591 Interface consists of two parts: the Smart Wireless Field

Link that provides the radio link to the

Wireless

HART field devices,

and the IEC 62591 Interface Module that installs into the ROC800.

Installation and

Configuration

The IEC 62591 Interface module connects to the Smart Wireless Field

Link through a four-wire connection. This allows the Smart Wireless

Field Link to be strategically placed away from the controller in the

optimal location for best network performance. The module provides

12 Vdc loop-output to power the Smart Wireless Field Link.

You can install one IEC 62591 Interface module in any slot on a

ROC800. Modules can be easily installed or removed from the module

slots at any time by removing the two captive screws accessible from

the front of the unit.

IEC 62591 Interface modules are hot-swappable, meaning the module

can be removed and another module of the same kind can be installed.

IEC 62591 Interface modules are hot-pluggable, meaning they may be

installed directly into unused module slots under power.

The module has a removable terminal block for convenient wiring and

servicing. The terminal block can accommodate size 24 to 16 American

Wire Gauge (AWG). A USB port is provided on the module to perform

firmware updates and to provide debug information to support

personnel.

Figure 4-41. Wiring on IEC62591 Module